Focus: Fire-Life Safety / Column

Q&A: Doors wedged open

Brad Keyes discusses restrictions on doors wedged open

By Brad Keyes / Special to Healthcare Facilities Today


Q: It has been our practice to not allow door hold open wedges on any door within the hospital. As far as code requirements go is it rated doors only, or does it include any door with a closer?

A: It applies to any fire rated door assembly, any non-rated door assembly that is required to be self-closing, and all corridor doors regardless of their fire-rating and regardless if they are self-closing.

Look at section 19.3.6.3.10 of the 2012 LSC, which says doors shall not be held open by devices other than those that release when the door is pushed or pulled. This section is part of section 19.3.6.3 "Corridor Doors" so it is referring to corridor doors only. Approved ‘push or pull’ release devices to hold a door open are the friction-fit type hold open that are integral to the door closer, and magnets. The logic here is a person could quickly push or pull the door closed, but if the door was wedged open, then the closing of the door would be slower and more difficult; therefore, wedging a door open would not be permitted.

Section 19.3.7.8 (1) of the 2012 LSC says doors in smoke barriers must be self-closing. The term 'self-closing' means the door has to close by itself without assistance. A smoke barrier door that is wedged open will not close by itself. Section 3.3.238 of the 2012 LSC defines "Self-closing" as a door equipped with an approved device that ensures closing after opening. All doors in hazardous areas are required to be self-closing regardless if the door is fire-rated or just smoke resistant.

To further make the point, section 19.2.2.2.7 of the 2012 LSC says any door in an exit passageway, stairway enclosure, horizontal exit, smoke barrier, or hazardous area enclosure shall be permitted to be held open only by automatic release device that complies with 7.2.1.8.2. The implication here is these doors must be self-closing and may only be held open by a device that releases the door (and allows the door to self-close) upon activation of the fire alarm system or sprinkler system.  

And to finally address fire-rated door assemblies, section 8.3.3.1 requires all doors required to have a fire protection rating to comply with NFPA 80, which requires self-closing devices on the doors. So, any fire-rated door assembly may not be wedged open.

That applies to nearly all doors in a hospital. But there are some doors that you could actually wedge open, although you probably would not want to inform your staff. Doors located inside a suite of rooms that do not serve an exit or a hazardous area would be permitted to be wedged open because those rooms inside a suite are not required to have doors. But that's about it.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 



January 25, 2017


Topic Area: Regulations, Codes & Standards


Recent Posts

Rethinking Strategies for Construction Success

Encouraging project team stakeholders to communicate, collaborate, care and align around a common goal.


From Touchless to Total Performance: Healthcare Restroom Design Redefined

Facility managers are raising the bar on hygiene, durability and system performance by turning restrooms into frontline assets for infection prevention and patient confidence.


New York State Approves $53M Construction Program at Niagara Falls Memorial Medical Center

DOH greenlights first $6.5M phase, launching campus-wide upgrades to clinical spaces, infrastructure and patient care services through 2027.


How Health Systems Are Rethinking Facilities Amid Margin Pressure

As insurance uncertainty and consolidation reshape healthcare, facilities managers are turning to efficiency, adaptability and portfolio optimization to control costs.


Ground Broken on New Medical Office Building in Scottsdale, AZ

Hammes is developing a new 34,000-square-foot medical office building in Scottsdale, Arizona, in partnership with Phoenix-based NOVO Development.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.