Unlocking the code to fire safety equipment compliance

To ensure compliance with this standard, hospital facility directors should be familiar with the related code requirements themselves and knowledgeable about their interpretation

By Healthcare Facilities Today


Despite increased attention to fire and life safety in recent years, there has not been a noteworthy decrease in the noncompliance rate with the Environment of Care Standard EC.02.03.05 that addresses the requirements for maintenance, testing and inspection of fire safety equipment and building features, according to an article on the FacilityCare website.

Standard EC.02.03.05 repeatedly makes The Joint Commission’s top 10 list of most frequently cited standards.

 To ensure compliance with this standard, it is critical for hospital facility directors to be familiar with the related code requirements themselves and knowledgeable about their interpretation, the article that takes a look at some of the most challenging requirements under EC.02.03.05, as well as discuss changes related to the upcoming adoption of the NFPA 101 Life Safety Code 2012 edition.

 This first article in a series focuses on Element of Performance (EP) 1, which addresses the requirements for supervisory signal devices.

 EC.02.03.05-EP1 states: “At least quarterly, the hospital tests supervisory signal devices (except valve tamper switches). The completion date of the tests is documented. NFPA 72 1999 edition groups and classifies a supervisory signal device as an “initiating device,” along with smoke detectors, heat detectors, and manual pull stations.

Per NFPA definition, a supervisory signal initiating device is “an initiating device such as a valve supervisory switch, water level indicator, or low air pressure switch on a dry-pipe sprinkler system in which the change of state signals an off-normal condition and its restoration to normal of a fire protection or life safety system; or a need for action in connection with guard tours, fire suppression systems or equipment, or maintenance features of related systems.” 

These supervisory signal devices shall be tested on a quarterly basis, except for control valve switches, the article said.

 NFPA 72 1999 edition lists five types of initiating supervisory signals: control valve switch, high- or low-air pressure switch, room temperature switch, water level switch and water temperature switch.

According to the article, the complete list of supervisory signals goes beyond these five types listed. Supervisory signals, in general, often are overlooked during the testing, inspection and maintenance of the fire alarm system.

Once the 2012 version of the Life Safety Code is adopted, NFPA 72 2010 edition also lists two new types of supervisory signals in Table 14.4.5: “other suppression system supervisory initiating devices,” which have to be tested quarterly, and “other supervisory initiating devices,” which have to be tested annually.

Annex A (A.23.8.5.6) NFPA 72 2010 edition lists examples of supervisory signals, which include, but are not limited to:

• Control valves 1 ½ inches or larger.

• Pressure, including dry-pipe system air, pressure tank air, pre-action system supervisory air, steam for flooding systems and public water.

• Water tanks, including water level and temperature.

• Building temperature, including areas such as valve closet and fire pump house.

• Electric fire pumps, including running (alarm or supervisory), power failure and phase reversal.

• Engine-driven fire pumps, including running (alarm or supervisory), failure to start, controller off “automatic” and trouble (e.g., low oil, high temperature, overspeed).

• Steam turbine fire pumps, including running (alarm or supervisory), steam pressure and steam control valves.

Read the article.

 

 



January 20, 2014


Topic Area: Safety


Recent Posts

The OR HVAC Puzzle: Why Individual Systems Are on the Rise

Extra penetrations, tight clearances and strict humidity needs—design experts explain what it really takes to plan dedicated units for each operating room.


Sutter Health Announces Plans for New Santa Clara Medical Center

Sutter projects the medical center will open in late 2031.


Sanford Health Receives $300M Gift for Black Hills Medical Center Campus

Construction is scheduled to begin in 2027 with completion expected by 2030.


Wanted: Scientific Standard for Hospital Cleaning

No accepted criteria exist for defining a surface as clean using microbiologic methods.


NLCS Strengthens Safety and Compliance with Comprehensive Electrical Program

Case study: A renewed partnership with Siemens helps the senior living provider meet NFPA 70B standards, reduce risk, and enhance reliability across its communities.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.