In a recent Q&A on the FacilityCare website, consultant Brad Keyes answered a question about testing requirements for backflow preventers.
Q: Many authorities having jurisdiction are requiring reduced pressure zone backflow devices on sprinkler systems. Is there a testing requirement for these devices?
A: Yes, backflow preventers, both double-check and RPZ types, must be tested on an annual basis when connected to sprinkler systems. NFPA 25 requires all backflow preventers installed in fire protection system piping to be tested annually at the designed flow rate of the fire protection system.
The HVAC Dilemma: To Repair or Replace?
Department of Veterans Affairs Signs Lease for Community-Based Outpatient Clinic in Kentucky
Cameron Regional Medical Center Falls Victim to Ransomware Attack
3 Pillars of Stronger Cybersecurity in Healthcare
Meridian Acquires Medical Office Building in Pasadena, CA