In a recent Q&A on the FacilityCare website, consultant Brad Keyes answered a question about testing requirements for backflow preventers.
Q: Many authorities having jurisdiction are requiring reduced pressure zone backflow devices on sprinkler systems. Is there a testing requirement for these devices?
A: Yes, backflow preventers, both double-check and RPZ types, must be tested on an annual basis when connected to sprinkler systems. NFPA 25 requires all backflow preventers installed in fire protection system piping to be tested annually at the designed flow rate of the fire protection system.
Building Envelope Design: Beyond Energy Efficiency
Outpatient Surge Reshapes Long-Term Strategy for Medical Outpatient Buildings
Mercy Medical Center to Be Integrated into Baystate Health
Managing IAQ in Healthcare Facilities During Wildfires
Building Hospital Resilience in an Era of Extreme Weather