Backflow preventers Q&A

In a recent Q&A on the FacilityCare website, consultant Brad Keyes answered a question about backflow preventers


In a recent Q&A on the FacilityCare website, consultant Brad Keyes answered a question about testing requirements for backflow preventers. 

Q: Many authorities having jurisdiction are requiring reduced pressure zone backflow devices on sprinkler systems. Is there a testing requirement for these devices?

A: Yes, backflow preventers, both double-check and RPZ types, must be tested on an annual basis when connected to sprinkler systems. NFPA 25 requires all backflow preventers installed in fire protection system piping to be tested annually at the designed flow rate of the fire protection system.

Read the full answer.

 

 



August 26, 2014


Topic Area: Maintenance and Operations


Recent Posts

Building Hospital Resilience in an Era of Extreme Weather

Expert Jennifer Mahan discusses the vulnerabilities healthcare facilities face during disasters and the infrastructure strategies that keep operations running.


Ennoble Care Falls Victim to Data Breach

Their investigation into the incident is still ongoing.


USDA Invests $73.8M to Aid in Livingston Hospital Expansion

Livingston Hospital will use the loan to modernize and construct a 56,000-square-foot addition to the hospital.


Why A Skilled Cleaning Staff Matters in Operating Rooms

Operating rooms are high-risk zones for infection due to invasive procedures and vulnerable patients, so competence in cleaning is critical.


General Leonard Wood Community Hospital Opening Date Set

The medical facility is designed to provide care to service members, retirees and their families.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.