In a recent Q&A on the FacilityCare website, consultant Brad Keyes answered a question about testing requirements for backflow preventers.
Q: Many authorities having jurisdiction are requiring reduced pressure zone backflow devices on sprinkler systems. Is there a testing requirement for these devices?
A: Yes, backflow preventers, both double-check and RPZ types, must be tested on an annual basis when connected to sprinkler systems. NFPA 25 requires all backflow preventers installed in fire protection system piping to be tested annually at the designed flow rate of the fire protection system.
Making the Energy Efficiency Case to the C-Suite
How to Avoid HAIs This Flu Season
Design Phase Set to Begin for Hospital Annex at SUNY Upstate Medical
Building Hospital Resilience in an Era of Extreme Weather
Ennoble Care Falls Victim to Data Breach