Backflow preventers Q&A

In a recent Q&A on the FacilityCare website, consultant Brad Keyes answered a question about backflow preventers


In a recent Q&A on the FacilityCare website, consultant Brad Keyes answered a question about testing requirements for backflow preventers. 

Q: Many authorities having jurisdiction are requiring reduced pressure zone backflow devices on sprinkler systems. Is there a testing requirement for these devices?

A: Yes, backflow preventers, both double-check and RPZ types, must be tested on an annual basis when connected to sprinkler systems. NFPA 25 requires all backflow preventers installed in fire protection system piping to be tested annually at the designed flow rate of the fire protection system.

Read the full answer.

 

 



August 26, 2014


Topic Area: Maintenance and Operations


Recent Posts

The OR HVAC Puzzle: Why Individual Systems Are on the Rise

Extra penetrations, tight clearances and strict humidity needs—design experts explain what it really takes to plan dedicated units for each operating room.


Skanska Completes Renovation of Specialized Care Facility for Sutter Health

The project was delivered through a highly coordinated effort, utilizing advanced construction methodologies to maintain efficiency.


Whitfield Regional Hospital Reports June 2025 Data Breach

The organization will continually evaluate and modify its practices and internal controls to enhance the security and privacy of personal information.


Silent Undercount: HAI Deaths Are Far Higher Than Reported

Several critical factors help explain inaccurate data on deaths from healthcare-associated infections.


Ground Broken on Cleveland Clinic Avon Hospital Expansion Project in Ohio

The expansion is expected to be completed in 2029.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.