In a recent Q&A on the FacilityCare website, consultant Brad Keyes answered a question about testing requirements for backflow preventers.
Q: Many authorities having jurisdiction are requiring reduced pressure zone backflow devices on sprinkler systems. Is there a testing requirement for these devices?
A: Yes, backflow preventers, both double-check and RPZ types, must be tested on an annual basis when connected to sprinkler systems. NFPA 25 requires all backflow preventers installed in fire protection system piping to be tested annually at the designed flow rate of the fire protection system.
The OR HVAC Puzzle: Why Individual Systems Are on the Rise
Skanska Completes Renovation of Specialized Care Facility for Sutter Health
Whitfield Regional Hospital Reports June 2025 Data Breach
Silent Undercount: HAI Deaths Are Far Higher Than Reported
Ground Broken on Cleveland Clinic Avon Hospital Expansion Project in Ohio