Q: Do exit signs with battery backup require the same testing as emergency lighting in the path of egress as indicted in section 7.10.9.1 of the 2012 Life Safety Code?

A: Well… yes, but not exactly. Section 7.10.9.1 of the 2012 Life Safety Code requires all exit signs to be visually inspected for operation of the illumination sources at intervals not to exceed 30 days. That is a visual inspection and is not a 30-second test or an annual 90-minute test that you’re alluding to.

But section 7.10.9.2 says exit signs connected to, or provided with, a battery-operated emergency illumination source must be tested and maintained in accordance with 7.9.3, which is the section that requires a 30-second monthly test and a 90-minutes annual test of the battery system. So, you’re correct in that battery powered ‘Exit’ signs need to be tested monthly and annually just like battery powered emergency lights, but you just had the wrong code reference.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



November 8, 2017


Topic Area: Regulations, Codes & Standards


Recent Posts

Building Sustainable Healthcare for an Aging Population

Traditional responses — building more primary and secondary care facilities — are no longer sustainable.


Froedtert ThedaCare Announces Opening of ThedaCare Medical Center-Oshkosh

The organization broke ground on the health campus in March 2024.


Touchmark Acquires The Hacienda at Georgetown Senior Living Facility

The facility will now be known as Touchmark at Georgetown.


Contaminants Under Foot: A Closer Look at Patient Room Floors

So-called dust bunnies on hospital room floors contain dust particles that turn out to be the major source of the bacteria humans breathe.


Power Outages Largely Driven by Extreme Weather Events

Almost half of power outages in the United States were caused by extreme weather events.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.