Focus: Fire-Life Safety / Column

Life Safety Q&A: Operating room exit doors

Brad Keyes continues the discussion on operating room exit doors

By Brad Keyes / Special to Healthcare Facilities Today


Q: Are operating rooms required to have two (2) exit doors? I have not seen this room but am under the assumption it is between 400 and 500 square feet.

A: According to section 18.2.5.5.2 of the 2012 Life Safety Code, non-sleeping rooms of more than 2500 square feet must have not less than two exit access doors remotely located from each other. Since the operating room you described is 400 to 500 square feet, I would say you are under the threshold for having to meet the requirement to have two doors to the corridor. 

Now, if the surgery area is a suite, there would not be a requirement for two exit access doors until you reached a 2,500-square-feet total for the entire suite, which would include the operating room.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



July 19, 2017


Topic Area: Regulations, Codes & Standards


Recent Posts

Aligning Construction and Facility Activities to Minimize Problems

Project managers need to address risks early to prevent issues during construction and renovation projects.


Cooper University Health Care Breaks Ground on 'Project Imagine'

The groundbreaking launched the first phase of a $3 billion expansion of the Health Sciences Campus in Camden, New Jersey.


3 Employees Injured by Patient at Halifax Infirmary's Emergency Department

Police contained the threat and took the patient into custody.


How Architects Shape the Future of Healthcare Facilities

Healthcare architecture is more than just designing and building hospitals.


UNC Health, Duke Health Form Partnership for Stand-alone Children's Hospital

The partners plan to break ground together on the new NC Children’s campus by 2027.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.