In a recent Q&A on the FacilityCare website, consultant Brad Keyes answered a question about linen chute doors.
Q: Do linen chute doors in an existing structure have to be rated if the room that houses the linen chute is protected by a two-hour wall and the door for this room is rated at 90 minutes?
A: Yes they do. There is no exception in NFPA 82 for the chute doors in a vertical chute that opens into a room that has the same fire-resistive rating as the shaft.
Rethinking Strategies for Construction Success
From Touchless to Total Performance: Healthcare Restroom Design Redefined
New York State Approves $53M Construction Program at Niagara Falls Memorial Medical Center
How Health Systems Are Rethinking Facilities Amid Margin Pressure
Ground Broken on New Medical Office Building in Scottsdale, AZ