New column

Q&A: Are eyewash stations needed in all janitor's closets?

Brad Keyes says it all depends on your organization conducting a risk assessment, which should determine if an eyewash station is necessary

By Brad Keyes / Special to Healthcare Facilities Today


Healthcare Facilities Today is happy to announce that Brad Keyes, CHSP, will be writing a weekly Q&A column for our website.  Visit healthcarefacilitiestoday every Wednesday for Brad's column. Better yet visit us every weekday for news, insights and advice for healthcare facilities professionals.

Q: I have been told several different ways that our facility didn't have eye wash station in our janitor’s closet. So, I was told to purchase the single-use portable squeeze bottles, and I installed one in each janitor’s closet. Now, I'm told we can't use these as they are not ANSI approved. Not all of our janitor’s closets are near an eyewash station, and our chemicals used in these closets are not spillable, and they are located in a locked dispenser. Do I need an eyewash station in every janitor’s closet since the chemical would be diluted with water?

A: Well...Maybe yes and maybe no. It all depends on your organization conducting a risk assessment, which should determine if an eyewash station is necessary.

First, start with a review of the Safety Data Sheets (SDS) of the chemicals used in the work area (i.e. janitor’s closet). Does the SDS say to flush the eyes for 15 minutes? If so, then that is an indicator (but not necessarily a sure bet) that an eyewash station is needed. Next, evaluate the way that staff is using the chemical…. Is there a possibility that the chemical (even if it is diluted) can splash into the eyes of the individual? You make this determination assuming staff will NOT be wearing any PPE eye protection, because humans being the people that they are will eventually not wear their PPE.  

If the risk assessment determines that there is a risk of splash into the eyes by chemicals that require 15 minutes of flush, then yes, you do need an eyewash station. The eyewash station needs to be ANSI Z358.1-2014 approved and while most of these are plumbed eyewash stations, there are a few that meet the ANSI standard and are self-contained and cost much less.

The portable squeeze bottles are not an acceptable substitute for an ANSI Z358.1-2014 approved eyewash station, but they are not illegal to have. They can be used as a first-aid device, but usually they are just a red-flag to surveyors that there is something going on here.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs

 

 



June 15, 2016


Topic Area: Regulations, Codes & Standards


Recent Posts

17 Million Patient Records Stolen in PIH Health Ransomware Attack

A ransomware attack halted operations across three of PIH’s hospitals.


Holidays are Prime Times for Healthcare Cyberattacks

A study found that 86 percent of organizations that experienced ransomware attacks were targeted on a holiday or weekend.


Hartford Healthcare Forms Partnership to Open Health Equity Clinic

The new clinic will open in January 2025.


UCHealth Reveals Plans for Memorial Hospital North Expansion

Construction on the patient tower is slated for 2026 with a projected opening to patients in 2029.


What Are 'Hospi-tels'?

Hospitals and hotels are partnering to better cater to patients and families.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.