Focus: Fire-Life Safety / Column

Q&A: Five-year internal inspection of sprinkler systems

Brad Keyes discusses five-year internal inspections of sprinkler systems

By Brad Keyes / Special to Healthcare Facilities Today


Q: I listened in on your recent webinar when you introduced all of us to the changes with the new 2012 Life Safety Code. In regards to the section involving fire sprinklers you stated that we need to have a five-year internal inspection of the pipe at the end of the line and a branch to a sprinkler head. But you do not specify whether this applies to just wet systems or dry systems? Do we need to do this on both types of systems?

A: According to Section 14.2 (Internal Inspection of Piping) in NFPA 25-2011, here is what’s required:
 
• An inspection of piping and branch line conditions shall be conducted every 5 years by opening a flushing connection at the end of one main and by removing a sprinkler toward the end of one branch line for the purpose of inspecting for the presence of foreign organic and inorganic material.
 
Brad’s comments: According to the NFPA handbook for this section, you must open up both locations (a flushing location and a sprinkler) and examine the condition of the pipe inside both of these locations. The standard specifically wants you to look for the presence of Micro-biologically Influenced Corrosion (MIC), zebra mussels, or inorganic materials such as rust and scale, as well as other items that may have been left in place by the installers such as gloves and cut-out coupons. You’re looking for these items because they can cause obstructions. According to the handbook, looking in just two locations once every 5 years is sufficient and provides a reasonable assurance that the entire system is acceptable. This internal inspection should be coordinated when the system is drained for other internal inspections, such as check valves. The handbook specifically says this 5-year inspection applies to wet, dry, pre-action, and deluge systems, as well as foam-water sprinkler systems.
 
• Alternative non-destructive examination methods shall be permitted.

Alternative nondestructive examination methods includes the use of X-ray, ultrasound, and remote video techniques.

• Tubercules or slime, if found, shall be tested for MIC.

NFPA does not define what a tubercule is, but according to a dictionary, a tubercule (also spelled tubercle) is a nodule or small eminence, attached to the inside of the pipe. The reason NFPA wants tubercules and slime tested for MIC, is MIC is very destructive to the inside of a sprinkler pipe, and almost always leads to pinhole leaks. There is newer technology being used that injects nitrogen (taken from the atmosphere) into the sprinkler system when filling that lowers the level of oxygen to a point that prohibits MIC from growing.

• If the presence of sufficient foreign material is found to obstruct the pipe or sprinklers, then an obstruction investigation must be conducted as described in section 14.3.

NFPA does not say how much foreign material is sufficient to obstruct pipe or sprinklers, so this is a judgement call. It would be normal to observe small amounts of scale and rust inside sprinkler pipe and should not trigger an obstruction investigation.

• Non-metallic pipe shall not be required to be inspected internally.

Corrosion is associated with metallic pipe so non-metallic pipe (i.e. plastic CPVC) is not subject to the 5-year internal inspection.

• In dry systems and pre-action systems the sprinkler removed for inspection shall be from the most remote branch line from the source of water that is not equipped with the inspector’s test valve.

The dry system and pre-action system is required to have an inspector’s test valve, but NFPA does not want a sprinkler pulled on the branch line containing the inspector’s test valve. So, they want the sprinkler pulled on the next branch line closest to the branch line containing the inspector’s test valve.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs

Brad's next webcast is scheduled for Dec. 14. He'll be discussing  "New Requirements, New Challenges: The 2012 Life Safety Code."

 



November 30, 2016


Topic Area: Regulations, Codes & Standards


Recent Posts

Alleged Ransomware Administrator Extradited from South Korea

The Phobos ransomware has been used globally to target over 1,000 organizations, including healthcare.


Design Plans Unveiled for New Intermountain St. Vincent Regional Hospital

The new hospital will be a 14-floor, 737,000 square-foot facility in Billings, Montana.


Ground Broken on New Pediatric Health Campus in Dallas

The new campus will replace the existing Children’s Medical Center Dallas.


Pre-Construction Strategies for Successful Facilities Projects

Savvy decisions can help facilities meet long-term goals by creating consistency and eliminating waste.


Geisinger Finds Success with Violence Prevention Efforts

Their safety measures included training staff in de-escalation, active-shooter response drills and equipping 6,000 employees with duress notification badges.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.