Focus: Fire-Life Safety / Column

Q&A: Office door swing

Brad Keyes discusses office door swing requirements

By Brad Keyes / Special to Healthcare Facilities Today


Q: Does a corridor door that serves an office have to swing into the office? The office is on a patient floor and the door does not serve as any other type of door.

A: No. The door is permitted to swing into the corridor, but during its swing, it cannot obstruct more than ½ the width of the corridor. And when the door is fully open (up against the wall), it cannot extend more than 7 inches into the corridor.

If the door swings into more than ½ the width of the corridor, then that is a problem. Likewise, if the door extends out into the corridor more than 7 inches when it is fully opened, then that also is a problem.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs

 

 



October 26, 2016


Topic Area: Regulations, Codes & Standards


Recent Posts

UF Health Hospitals Rely on Green Globes to Realize Their Full Potential

Case study: The process encouraged the team to push themselves in several areas.


How Healthcare Facilities Can Be Truly Disaster-Resilient

Real resilience looks different than what’s written down in plans


TriasMD Breaks Ground on DISC Surgery Center for San Fernando Valley

It is set to open in Q3 2025


Bigfork Valley Hospital Falls Victim to Data Breach

The incident occurred in November 2024


AI-Driven Facilities: Strategic Planning and Cost Management 

6 factors to ensure infrastructure, operations and financial management support AI’s integration


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.