Q&A: Overhead rolling fire door

Brad Keyes discusses whether overhead rolling fire door is needed

By Brad Keyes / Special to Healthcare Facilities Today


Q: We have an existing overhead rolling fie door acting as a curtain-window between a phlebotomy area and the egress corridor that is no longer needed (like to those found in pharmacy areas to the corridor). It is currently connected to the fire system for release and also has a fusible link. We want to disconnect it from the fire system, keep it closed, and drywall the window area so that it does not appear it was ever there. The question arose, can this be done, or do we need to go through the cost to physically remove it. It is viewed by some that once it was in place it must always be tested and inspected unless completely removed. However, I see this as being similar to walling off a dumbwaiter with "2 hr. shaft-wall" when it is no longer needed. We have been allowed to do this by our state agency. What do you think?

A: I think your analogy is apt for this situation. According to sections 4.5.8 and 4.6.12.1 of the 2012 LSC, whenever a device is required for code compliance, it must be continuously maintained. But, if you close-up the opening in such a way that complies with new construction requirements, then the over-head rolling fire door is no longer needed. So, boxing in the device and abandoning in place would be acceptable.

And, according to section 4.6.12.3 of the 2012 LSC, existing life safety features obvious to the public, if not required by the code, must be either maintained or removed. Well, if you box-up and cover the overhead rolling fire door (and it is no longer required), then it is no longer obvious to the public and can be removed.

While my personal choice would be to remove the overhead rolling fire door if it is no longer needed and used, your plan to cover it up would be acceptable as long as it is no longer needed.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs

Brad's webcast is scheduled for today. He'll be discussing  "New Requirements, New Challenges: The 2012 Life Safety Code."

 



December 14, 2016


Topic Area: Regulations, Codes & Standards


Recent Posts

Designing Hospitals for Wellness

Thoughtfully designed spaces can transform the overall well-being of patients, staff and caregivers.


Baptist Health Announces New Cancer Care Center in Key West

The building will be two stories tall and span 4,300 square feet.


Waco Family Medicine Achieves Savings and Bold Design with Wood Selections

Case study: The healthcare facility incorporated over 25,000 square feet of wood and saved over $400,000.


Alleged Ransomware Administrator Extradited from South Korea

The Phobos ransomware has been used globally to target over 1,000 organizations, including healthcare.


Design Plans Unveiled for New Intermountain St. Vincent Regional Hospital

The new hospital will be a 14-floor, 737,000 square-foot facility in Billings, Montana.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.