Focus: Fire-Life Safety / Column

Regulations, Codes & Standards Q&A: Fire Damper Testing

Brad Keyes discusses regulations on fire damper testing

By Brad Keyes / Special to Healthcare Facilities Today


Q: We have a new hospital building that is opening this month. For documentation on commissioning, the fire damper report just says the technician visibly watched the dampers close. Is there a protocol for the test required initially, first year and then every six years? Do the technicians doing the commissioning need to show training and/or be certified on fire damper testing?

A: No… the technician conducting the fire damper test is not required to be certified or demonstrate any particular training requirements. All they have to demonstrate is knowledge and ability, which is not defined in the NFPA standards. Therefore, the hospital can determine who is qualified based on an evaluation of their knowledge and ability, and documented in writing in their HR file.

You are correct… the dampers must be documented that they closed properly upon installation, then one year after installation, then every six years thereafter for a hospital (every four years thereafter for non-hospitals). A documented report must list the location of each damper, and the following information:

  • Name of the individual performing the test
  • Affiliation of the individual performing the test
  • The signature of the individual performing the test
  • The name of the test (i.e. installation test, one-year test, six-year test)
  • The date in month/day/year format
  • The frequency of the test
  • The NFPA standard and edition used to conduct the test
  • The results of the test such as ‘Pass’ or ‘Fail’ for each individual damper.

While many service companies provide pictures of the damper open and closed, NFPA does not require pictures to be taken.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



November 11, 2020


Topic Area: Regulations, Codes & Standards


Recent Posts

Mature Dry Surface Biofilm Presents a Problem for Candida Auris

Multiple methods are described in the literature, but no consensus has been reached for disinfection efficacy tests against biofilms.


Sutter Health's Arden Care Center Officially Opens

With an adaptive reuse of an underutilized office building, the 70,000 square-foot facility was renovated to meet current healthcare standards.


Insight Hospital and Medical Center Falls to Data Breach

The investigation determined that an unauthorized individual accessed the network between August 22, 2025, and September 11, 2025.


The High Cost of Healthcare Violence

As workplace violence increases, healthcare facilities face mounting financial and operational disruptions- prompting legislative action.


EVS Teams Can Improve Patient Experience in Emergency Departments

A report confirmed that cleanliness of the ED was the third most impactful element on patient experience surveys.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.