Focus: Fire-Life Safety / Column

Regulations, Codes & Standards Q&A: Hole in the wall

Brad Keyes discusses regulations for a hole in the wall

By Brad Keyes / Special to Healthcare Facilities Today


Q: I have a surgery suite that had a hole punched into the wall by the door knob. Is there anything in LSC that states " if a hole is made in a surgery wall the drywall needs to be replaced from stud to stud", not just repair the hole?

A: No… The LSC does not concern itself with the way the walls are constructed. When it comes to walls, the LSC only concerns itself with identifying which walls must be smoke resistant, fire-rated, or smoke rated. The UL listings for the walls will determine how the wall is constructed.

Now, if the wall with the door knob hole is only required to be smoke resistant, then you can seal the hole with any type of patch that makes the wall resistant to the passage of smoke. But if the wall is fire-rated, or is required to be a 1-hour rated smoke barrier, then you must excise the hole from stud to stud, insert a new piece of gypsum board, and screw, tape and apply joint compound in accordance with the UL listing for that wall.

I’m sure your Infection Control practitioner would have a lot to say about a hole in a wall in surgery.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



October 31, 2018



Recent Posts

Healthcare Real Estate: Challenges and Industry Shifts for 2025

The hurdles include balancing expansion with financial constraints, the sustainability of office and retail conversions, and technological disruptions.


Geisinger to Build $32 Million Cancer Center in Pennsylvania

The two-story, 40,000-square-foot facility will be home to the cancer center with space for future growth of services.


Sunflower Medical Group Experiences Data Breach

To date, Sunflower has no evidence that personal information has been misused.


Strategies to Eradicate Biofilm Containing C. Auris

Understanding the speed and risks of contamination after room disinfection should inform managers’ environmental cleaning recommendations.


Man Attacks Nurses, Police Officer at Jefferson Hospital

The man allegedly attacked the staff members before being restrained and sedated.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.