Focus: Regulations, Codes & Standards

Regulations, Codes & Standards Q&A: Missing ceiling tiles

Brad Keyes discusses regulations for missing ceiling tiles

By Brad Keyes / Special to Healthcare Facilities Today


Q: Do missing ceiling tiles in a suspend create a Life Safety Code deficiency in an existing business occupancy? Should section 4.6.12.2 of the 2012 Life Safety Code apply to require the maintenance of broken or missing ceiling tiles in a business occupancy?

A: The complete membrane that the ceiling forms is required if sprinklers or smoke (or heat) detectors are installed in the room or area served by the ceiling. The ceiling acts to trap the heat and smoke and allows the sprinklers or detectors to operate.  

Otherwise, if a ceiling tile is missing, or has excessive gaps around penetrations, or the ceiling tiles have holes, then heat and smoke can continue up into the interstitial space above and the operation of the sprinklers and/or detectors would be delayed, thus causing an impairment.

If there are no sprinklers or smoke (or heat) detectors in the room or area, then there may not be any Life Safety Code reason for the ceiling system, unless it serves as part of the fire-rated floor/ceiling system, such as UL-G227 or UL-G235. Section 4.6.12.2 would not apply if the ceiling is not serving a purpose of life safety.

Now, the suspended grid and tile ceiling may serve an Infection Control purpose, and you would have to maintain it for that reason, but that is not a Life Safety Code purpose.

Yes… this would apply to business occupancies. It is not dependent on any particular occupancy.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 



January 10, 2018


Topic Area: Regulations, Codes & Standards


Recent Posts

Building Sustainable Healthcare for an Aging Population

Traditional responses — building more primary and secondary care facilities — are no longer sustainable.


Froedtert ThedaCare Announces Opening of ThedaCare Medical Center-Oshkosh

The organization broke ground on the health campus in March 2024.


Touchmark Acquires The Hacienda at Georgetown Senior Living Facility

The facility will now be known as Touchmark at Georgetown.


Contaminants Under Foot: A Closer Look at Patient Room Floors

So-called dust bunnies on hospital room floors contain dust particles that turn out to be the major source of the bacteria humans breathe.


Power Outages Largely Driven by Extreme Weather Events

Almost half of power outages in the United States were caused by extreme weather events.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.